Setting up External Serial ports is easy on
a Do-more enabled 205 base. Just go to the PLC >> System Configuration,
Module Configuration(s) This lists all the modules currently plugged into our base. We only have one so we’ll select that and
edit it. Let’s give it a name – This will be our
“Aux Serial” – and we’re going to plug our control panel into port 1 so let’s
call that “C_More_Micro” since that is the panel we’ll be using. He’ll be serving as an RTU Sever so we’ll
apply that. And then we need to check our device settings. Let’s see … that C-More Micro runs at
9600 baud, so we need to fix that and everything else looks ok. We need to make sure this address matches
that of the C-more Micro and “1” is the right address. So we are good to go there, good to go here. And click OK. We get a little warning -= these changes can’t
take effect until we are in program mode and we download it to the Do-more processor. We’re good to go there so we’ll go ahead. That’s it we’re done. That’s all there is to setting up the external
serial port. Let’s try it and make sure it works. The C-More Micro control panel is plugged
into port A of my external serial port module here and it is all powered up. When I press the graphical buttons on the
C-More Micro Panel, I can see the reaction here in the Do-more. When that lit up, it lit up this very quickly
- which is C203 – which C203 is right here which ran this routine which is now done. So our external serial port is working exactly
as expected. Now this business I have going on right here
is to emphasize a point. Remember that on the DoMore … Modbus devices
CANNOT modify any system resources – they can’t directly modify any of these memory
blocks for example - they can only modify this protocol section, Modbus server, these
four blocks memory right here. These are dedicated to al Modbus commands. That’s a great security feature because
now you control all of the information that comes and goes via Modbus and can validate
it before it has an impact on your system. That’s why we had this Modbus bit NOT directly
enabling this routine – this rung is meant to be a place holder/reminder for us to add
security checks in the future. Could the Modbus command have directly driven
this routine? Sure. If you want to see how to setup the C-More
Micro to talk to the DoMore – go to www.cmoremicro.com/support. There are lots of videos there that will show
you how. Using external serial ports is a new powerful
feature with the DoMore – you couldn’t simply add extra serial ports on a 205 rack
before – now with the DoMore it’s easy to add as many serial ports as you need! We’ll, That’s all there is to setting
up the DoMore to work with an HMI. Be sure to check out the other videos in this
series to get the most out of the DoMore processor. And as always, please send us any topics you
would like to see covered – or - any other comments for that matter – we appreciate
the feedback! Spend Less. DoMore. From AutomationDirect.